S708-60
Literature download pdf
Application Notes download pdf
Type Water-based Intumescent Basecoat
Properties Area of Use Internal/Semi Exposed
Specific Gravity (SG) 1.38
Volume Solids 70% +-2%
Flash Point N/A
Colour White
Technical Preparation Onto clean dry compatible primer
WFT (microns) Brush: <1000  Spray: <1600
DFT (microns) Brush: <700  Spray: <1120
Drying Time 24 hour between coats at >10°C
Over Coating Minimum 24 hours at >10°C before top seal application
Fire Performance 30 and 60 minutes
Steel Section Universal beams and columns, cellular beams
Certification FIRE
BS 476:Parts 20/21, BS 476: Parts 6/7 Class O,
EN13823 (SBI) and IMO smoke/toxicity

DURABILITY
ETAG018 Part 2 2006
Top Seal Requirement Internal Environments C1 & C2 No top seal required. TS816WAC for decorative finish optional
Permanently Semi-exposed Environments No top seal required. TS815SAC for decorative finish optional
Construction Phase Durability : Up to six months fully exposed No top seal required. TS815SAC or TS818WPU for decorative finish optional
Greater than six months fully exposed Consult Nullifire Technical Desk
General Application Method Airless spray, short pile roller or brush
Container Size 25kg drum