| S708-60 |
| Literature |
download pdf |
| Application Notes |
download pdf |
| Type |
Water-based Intumescent Basecoat |
| Properties |
Area of Use |
Internal/Semi Exposed |
| Specific
Gravity (SG) |
1.38 |
| Volume
Solids |
70%
+-2% |
| Flash
Point |
N/A |
| Colour |
White |
| Technical |
Preparation |
Onto
clean dry compatible primer |
| WFT (microns) |
Brush: <1000 Spray: <1600 |
| DFT (microns) |
Brush: <700 Spray: <1120 |
| Drying Time |
24 hour between coats at >10°C |
| Over Coating |
Minimum 24 hours at >10°C before top seal application |
| Fire Performance |
30 and 60 minutes |
| Steel Section |
Universal beams and columns, cellular beams |
| Certification |
FIRE
BS 476:Parts 20/21, BS 476: Parts 6/7 Class O,
EN13823 (SBI) and IMO smoke/toxicity
DURABILITY
ETAG018 Part 2 2006 |
| Top Seal
Requirement |
Internal Environments C1 & C2 |
No top seal required. TS816WAC for decorative finish optional |
| Permanently Semi-exposed Environments |
No top seal required. TS815SAC for decorative finish optional |
| Construction Phase Durability : Up to six months fully exposed |
No top seal required. TS815SAC or TS818WPU for decorative finish optional |
| Greater than six months fully exposed |
Consult Nullifire Technical Desk |
| General |
Application
Method |
Airless
spray, short pile roller or brush |
| Container Size |
25kg
drum |