| S607HB |
| Literature |
 |
| Application Notes |
 |
| Type |
Water-Bourne
Intumescent Basecoat |
| Properties |
Area of Use |
Internal |
| Specific
Gravity (SG) |
1.39 |
| Volume
Solids |
62%
+-2% |
| Flash
Point |
>55°C |
| Colour |
White |
| Technical |
Preparation |
Onto
clean dry compatible primer |
| WFT (microns) |
Brush: <1000
Spray: <1600 |
| DFT (microns) |
Brush: <620
Spray: <992 |
| Drying Time |
24
hours between coats at >100C |
| Over Coating |
Minimum
24 hours at >100C before top coat |
| Fire Performance |
30,
60 and 90 minutes |
| Steel Section |
Universal
and hollow steel sections |
| Certification |
BS476:Part
20/21:1987 ASFP Approved |
| Top Seal
Requirement |
Over
Coating |
Top
seal within 1 month |
| Building Classification |
C2
and C3 buildings |
| General |
Application
Method |
Airless
spray, short pile roller or brush |
| Container Size |
25kg
drum |