| System
E |
| Literature |
 |
| Application Notes |
 |
| Type |
High
performance Epoxy Intumesent Coating |
| Properties |
Area of Use |
Internal
or External |
| Specific
Gravity (SG) |
1.1 |
| Volume
Solids |
100% |
| Flash
Point |
100°C |
| Colour |
Blue |
| Technical |
Preparation |
Onto
clean dry compatible primer |
| WFT (microns) |
4-5mm |
| DFT (microns) |
4-5mm |
| Drying Time |
Less
than 24 hours |
| Over Coating |
Maximum
48 hours before top coat |
| Fire Performance |
Upto
3 hours cellulosic Upto 4 hours hydrocarbon |
| Steel Section |
Universal
and hollow steel sections |
| Certification |
BS476:Part
20/21:1987, UL, IMO and Lloyds certified |
| Top Seal
Requirement |
Over
Coating |
Refer
to Nullifire technical department |
| Building Classification |
Refer
to Nullifire technical department |
| General |
Application
Method |
Airless
spray, trowel and casting |
| Container Size |
22.7kg
kits |